DESIGN NO. TRC/PV 60-07
VERTICAL (WALL), RATINGS: CAN/ULC-S115 1 HOUR (F, FT, FTH); ANNULAR SPACING 1/16" MIN. & 3/16" MAX. - ABS PENETRATIONS, ANNULAR SPACING 1/16" MIN. & 3/8" MAX. - PVC PENETRATIONS
TEST PRESSURE DIFFERENTIAL - 50 Pa (0.20" OF WATER)


Manufacturer's Designation: Pipe Collar GW-20.
 


 

Wall: Minimum nominal 2 x 4 wood or steel stud framed gypsum wallboard faced wall assembly, providing a 1 hour rating.
Penetrations: Max. 4" diameter SCH 40 or 6" diameter PVC, ABS, DWV or process and supply, cellular core or solid.
Metacaulk® Pipe Collar: Size appropriately for pip fastened to both sides of gypsum wall assembly in accordance with Rectorseal Corp. installation instructions.
Metacaulk® 1000: Optional - Sealant installed to a depth of 1/2".